7 - 13
INP-TN4PHAV-E
7.8
Setting kind of input, skip, unit, filter, scaling, subtraction
The type of input (B, R, S, K, E, J, T, N, W, L, U, PN thermocouples, JPt, Pt, voltage, COM, copy
skip), units (
°
C,
°
F, mV, V), filters (time constant) and in the case of DC voltage input, the scaling,
input range, engineering value (scaling value), units, rooters (square root extractors) and logarithmic
arithmetic operation are specified for each channel.
= Explanation of display =
Channel No.
Type of input
Unit (°C, °F, mV, V)
0 to 900
C h
F i l t e r
T =
s e c
Note:
* When skip is set as the input type, indication, recording and alarming actions are not performed for
the subject channel.
Explanation
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
ENT
Ch
FILTER
T=
sec
In the case of
thermocouples,
resistance bulbs
Ch1
K
°C
FILTER T=3 SEC
Ch1
50mV
mV
FILTER T=3 SEC
Ch1
COM
FILTER T=3 SEC
Ch2
COPY
Ch2<=Ch3
Ch1
SKIP
FILTER T=3 SEC
In the case of DC
voltage (current)
In the case of
transmission input
Set copy
Skip
SUBTRACTION
Ch1
Ch0
Ch1
MEASUR. RANGE
0 to 10.00mV
Ch1 SCALING=ON
If OFF
Ch1 SQUARE ROOT OFF
LOGARITHM OFF
Ch1 ENG. VALUE
0 to 10.00
Ch1 UNIT
CODE
kg/h
A=3 B=2
SUBTRACTION
Ch0
Ch1
Ch1
0-100000 of transmission
input data is converted into
the min. - max. of an
industrial value.
To the next channel
Next channel
Note:
Data copied by the copy
which has been set.
• Type of input
• Filter
• Scaling
• Subtraction
• Rooter
• Recording range
• Unit
• Zone set value
• Zoom set value
• TAG No.
• Alarm set value
Note:
When skip is set, the
formerly set engineering
value, unit, etc. are reset.
On the occasion of the next
measurement (when an
input type other than skip is
set), set engineering value,
unit, etc. once again.