7-2-2 Malfunctions Followed by Alarms
(1) Overcurrent
1) Vector control and sensorless vector control
Over current IPM Error
OC IPE
YES
YES
YES
NO
YES
YES
YES
YES
NO
NO
YES
NO
NO
NO
NO
NO
Is inverter output wiring (U, V, W)
short-circuited to ground?
(Disconnect output wiring and make
sure no continuity with ground)
Is inverter inside wiring
short-circuited to ground?
(Make sure no continuity
between U, V, or W terminal
of motor and ground)
Did overcurrent happen during motor
parameter tuning
(function code H01).
Is sensoless control
(code P01 or A01) selected?
Is PG pulse number specification
correct?
Are there any problems with wiring
from PG?
- Is shield line connected wrongly?
- Is signal line or power line
disconnected?
- Is signal line twisted with power line?
Is PG defective?
Use oscilloscope to check PG waveform.
Inverter fault is suspected.
Contact FUJI.
Did overcurrent alarm occur on rapid
acceleraion/deceleration?
Eliminate ground fault.
You must replace motor.
Contact FUJI.
Increase data for exciting current
(function code P08 or A10)
and execute motor parameter
tuning again.
Specify again according to motor PG.
Adjust wiring.
Replace motor PG.
Increase acceleration/deceleration times
(code F07, F08, C46, C47, C56, C57,
C66 or C67) longer and operate.
NO
YES
Is the carrier frequency setting
between 2 and 15kHz?
Specify the carrier frequency setting
between 2 and 15kHz.
Содержание 5000VG7S Series
Страница 7: ...0 6 Warning Label Position for Inside the Inverter...
Страница 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Страница 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Страница 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Страница 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...