7-23
(14) Memory error (Er1)
Review the function data before you turn off the power when the memory error occurs. When the data
are correct, the error is limited to data in the back up memory. Only if you can use "All save" to save data
without reoccurence of Memory error, you can operate the inverter. Check the printed circuit board
visually for dusts.
When the function data are abnormal, or memory error occurs frequently while function data are normal,
an inverter fault is suspected. Contact FUJI
.
(15) KEYPAD panel communication error
KEYPAD panel communication error
Er2
Turn off power supply
and charge lamp,
then turn on again.
Inverter is defective.
Contact FUJI.
YES
Treat defective part.
Inverter is normal.
You can continue to
operate.
If KEYPAD panel
communication error
occurs frequently,
inverter fault is
suspected.
Contact FUJI.
YES
Related code: F02
NO
NO
Are KEYPAD panel
connector and
socket inserted
firmly?
Does KEYPAD
panel display normal
data?