5-4
E: Extension Terminal Functions
Communication
address
Fcode
485
number
Link number
Function name
Setting range
e01
101h 120( 78 h) X1 terminal
function
0 to 63
0 to 3 : Multistep speed selection (1 to 15 steps)
(0 : SS1, 1 : SS2, 2 : SS4, 3 : SS8)
4, 5 : ASR and ACC/DEC time selection (4 steps)
(4 : RT1, 5 : RT2)
6 : 3 wire operation stop command (HLD)
7 : Coast-to-stop command (BX)
8 : Alarm reset (RST)
9 : External Alarm (THR)
10 : Jogging operation (JOG)
11 : Speed setting 2 / Speed setting 1 (N2/N1)
12 : Motor M2 selection (M-CH2)
13 : Motor M3 selection (M-CH3)
14 : DC brake command (DCBRK)
15 : ACC/DEC cleared to zero (CLR)
16 : Creep speed switching in UP/DOWN control
(CRP-N2/N1)
17 : UP command (UP)
18 : DOWN command (DOWN)
19 : Write enable for KEYPAD (WE-KP)
20 : PID control cancel (N/PID)
21 : Inverse mode changeover (IVS)
22 : Interlock signal for 52-2 (IL)
23 : Write enable through link (WE-LK)
24 : Operation selection through link (LE)
25 : Universal DI (U-DI)
26 : Pick up start mode (STM)
27 : Synchronization command (PG (PR) optional
function) (SYC)
28 : Zero speed locking command (LOCK)
29 : Pre-exiting command (EXITE)
30 : Speed reference limiter cancel (N-LIM)
(Related function : F76, F77, F78)
31 : H41 [torque reference] cancel (H41-CCL)
32 : H42 [torque current reference] cancel (H42-CCL)
33 : H43 [magnetic flux reference] cancel (H43-CCL)
34 : F40 [torque limiter mode 1] cancel (F40-CCL)
35 : Torque limiter 2 / Torque limiter 1 (TL2/TL1)
36 : Bypass from ramp function generator (BPS)
37, 38 : Torque bias reference 1/2
(37 : TB1, 38 : TB2)
39 : DROOP selection (DROOP)
40 : Zero hold command for Ai1 (ZH-AI1)
41 : Zero hold command for Ai2 (ZH-AI2)
42 : Zero hold command for Ai3 (option) (ZH-AI3)
43 : Zero hold command for Ai4 (option) (ZH-AI4)
44 : Ai1 polarity change (REV-AI1)
45 : Ai2 polarity change (REV-AI2)
46 : Ai3 polarity change (option) (REV-AI3)
47 : Ai4 polarity change (option) (REV-AI4)
48 : Inverse mode of PID output (PID-INV)
49 : PG alarm cancel (PG-CCL)
50 : Undervoltage cancel (LU-CCL)
51 : Ai torque bias hold [H-TB]
52 : STOP1 (The motor stops with normal deceleration
time.) (STOP1)
53 : STOP2 (The motor stops with deceleratime 4)
(STOP2)
54 : STOP3 (The motor stops with max, torque.)
(STOP3)
55 : DIA data latch (DIA option) (DIA)
56 : DIB data latch (DIB option) (DIB)
57 : Mulitiwinding motor cancel (SI (MWS) option)
(MT-CCL)
58 to 63 : Option Di 1/2/3/4/5/6 (O-DI1 to 6)
e02
102h 121( 79 h) X2 terminal
function
0 to 1 to 63
e03
103h 122( 7A h) X3 terminal
function
0 to 2 to 63
e04
104h 123( 7B h) X4 terminal
function
0 to 3 to 63
e05
105h 124( 7C h) X5 terminal
function
0 to 4 to 63
e06
106h 125( 7D h) X6 terminal
function
0 to 5 to 63
e07
107h 126( 7E h) X7 terminal
function
0 to 7 to 63
e08
108h 127( 7F h) X8 terminal
function
0 to 8 to 63
e09
109h 128( 80 h) X9 terminal
function
0 to 9 to 63
e10
10Ah 129( 81 h) X11 terminal
function
0 to 25 to 63
e11
10Bh 130( 82 h) X12 terminal
function
0 to 25 to 63
Communication
address
Fcode
485
number
Link number
Function name
Setting range
e12
10Ch 131( 83 h) X13 terminal
function
0 to 25 to 63
e13
10Dh 132( 84 h) X14 terminal
function
0 to 25 to 63
e14
10Eh
( h) X terminal
function
normal
open/closed
0000 to 01FF
Setting of normal state of X1-X9.
0 : Normally open
1 : Normally closed
e15
10Fh 133( 85 h) Y1 terminal
function
0 to 1 to 47
0 : Inverter running (RUN)
1 : Speed existence signal (N-EX)
2 : Speed agreement signal (N-AG)
3 : Speed egilivarent signal (N-AR)
4 : Speed level detection 1 (N-DT1)
5 : Speed level detection 2 (N-DT2)
6 : Speed level detection 3 (N-DT3)
7 : Stopping on undervoltage (LU)
8 : Detected torque polarity (Braking/Driving) (B/D)
9 : Torque limiting (TL)
10 : Torque detection 1 (T-DT1)
11 : Torque detection 2 (T-DT2)
12 : KEYPAD operation mode (KP)
13 : Inverter stopping (STP)
14 : Operation ready output (RDY)
15 : Magnetic flux detection signal (MF-DT)
16 : Motor M2 selection status (SW-M2)
17 : Motor M3 selection status (SW-M3)
18 : Mechanical brake release signal (BRK)
19 : Alarm indication signal 1 (AL1)
20 : Alarm indication signal 2 (AL2)
21 : Alarm indication signal 4 (AL4)
22 : Alarm indication signal 8 (AL8)
23 : Fan operation signal (FAN)
24 : Auto-resetting (TRY)
25 : Universal DO (U-DO)
26 : Heat sink overheat early warning (INV-OH)
27 : Synchronization completion signal (SY-C)
28 : Lifetime alarm (LIFE)
29 : Under acceleration (U-ACC)
30 : Under deceleration (U-DEC)
31 : Inverter overload early warning (INV-OL)
32 : Motor overheat early warning (M-OH)
33 : Motor overload early warning (M-OL)
34 : DB overload early warning (DB-OL)
35 : Link transmission error (LK-ERR)
36 : Load adaptive control under limiting (ANL)
37 : Load adaptive control under calculation (ANC)
38 : Analog torque bias hold (TBH)
39 to 47 : Option DO1 to 9 (O-DO1 to O-DO9)
e16
110h 134( 86 h) Y2 terminal
function
0 to 2 to 47
e17
111h 135( 87 h) Y3 terminal
function
0 to 3 to 47
e18
112h 136( 88 h) Y4 terminal
function
0 to 4 to 47
e19
113h 137( 89 h) Y5 terminal
function
0 to 14 to 47
e20
114h 138( 8A h) Y11 terminal
function
0 to 26 to 47
e21
115h 139( 8B h) Y12 terminal
function
0 to 26 to 47
e22
116h 140( 8C h) Y13 terminal
function
0 to 26 to 47
e23
117h 141( 8D h) Y14 terminal
function
0 to 26 to 47
e24
118h 142( 8E h) Y15 terminal
function
0 to 26 to 47
e25
119h 143( 8F h) Y16 terminal
function
0 to 26 to 47
e26
11Ah 144( 90 h) Y17 terminal
function
0 to 26 to 47
e27
11Bh 145( 91 h) Y18 terminal
function
0 to 26 to 47
e28
11Ch
( h) Y terminal
function
normally
open/closed
0000 to 001F
Setting of normal state of Y1to Y4,RY.
0 : Normally open
1 : Normally close
You can change the setting of a function indicated by during operation.
You should stop operation to change the setting of other functions.
Underline indicates a factory setting.
Items without underline have different factory settings according to capacity.
Содержание 5000VG7S Series
Страница 7: ...0 6 Warning Label Position for Inside the Inverter...
Страница 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...