7-5
3) Motor runs only at low speed
Motor runs at low speed roughly equivalent to slip
frequency and does not accelerate.
Continued operation presents alarm trip OL1, 2, or 3.
NO
NO
Inverter fault is
suspected.
Contact FUJI.
NO
NO
NO
YES
YES
YES
YES
YES
NO
YES
Is sensoless control
(code P01 or A01)
selected?
Is data of PG pulse
number correct
(code P28, A29,or A30)?
Is phase sequence of
wiring from PG correct?
Is wiring connected?
Is shield for wiring
installed correctly?
Is main circuit wiring
(U, V, W) between
inverter and motor
connected correctly?
Do motor parameters
(function code P and A)
match companion
motor?
YES
Does power supply
voltage (specification) of
PG and power supply
voltage (SW5) of PGP
match?
NO
Rewrite data according
to motor PG.
Adjust wiring.
Change data of function
code P02 to match.
Execute motor
parameter tuning
(function code H01).
Is motor dedicated
to VG7?
Reconfigure SW5.