2-1
2. Installation and Connection
2-1 Operating Conditions
Install the product under the conditions specified in Table 2-1-1.
Table 2-1-1 Operating Conditions
Item
Requirement
Place
Indoor
Ambient
temperature
-
10 to +50°C
Relative humidity
5% to 95% (no condensation allowed)
Atmosphere
The product should not be exposed to dust, direct
sunlight, corrosive gas, oil mist, vapor, waterdrops, or
air containing much salt.
No condensation should occur due to sudden
temperature changes.
Altitude
1,000m or less (if more than 1,000m, see Table 2-1-
2)
2 to 9Hz: 3mm amplitude
9 to 20Hz: 9.8m/s
2
(or 2m/s
2
for 200V, 75kW or
higher and 400V, 90kW or higher inverters)
Vibration
20 to 55Hz: 2m/s
2
55 to 200Hz: 1m/s
2
Table 2-1-2 Output Reduction Rates at Higher Altitudes
Altitude
Output Current Reduction Rate
1,000m or less
1.00
1,000-1,500m
0.97
1,500-2,000m
0.95
2,000-2,500m
0.91
2,500-3,000m
0.88