7-22
(12) NTC thermistor disconnection
(13) Charging circuit error
YES
NO
NO
Specify "Thermistor
selection (function
code P30,
A31 or A47)" again.
NTC thermistor
disconnection
nrb
Replace thermistor
with spare.
Inverter fault
is suspected.
Contact FUJI.
YES
NO
YES
Is motor provided with
thermistor?
Is motor thermistor
signal cable
disconnected
(THC-TH1)?
Does thermistor
disconnection alarm
occur?
Is motor ambient
temperature low
(-30 °C or less)?
NO
YES
Connect following
wiring diagram.
Thermistor is defective.
Operate with spare
thermistor.
Review operation
environment.
Charging circuit error
PbF
Inverter fault is
suspected.
Contact FUJI.
YES
NO
Is braking resistor
connection
incorrect?
You must replace
braking resistor
Adjust wiring.
NO
YES
Is braking resistor
disconnected?
Is resistance correct?
Change setting.
NO
YES
Is fan power supply
switching connector
set to R0-T0 side
by mistake
(see page 2-11)?