8-4
8-3 Measurement of Main Circuit Electrical Quantity
The indicated values depend on the type of meter because the harmonic component is included in the voltage
and current of the main circuit power (input) and the output (motor) side of the inverter. When measuring with
a meter for commercial power frequency use, use the meters shown in Table 8.3.1.
The power-factor cannot be measured using power-factor meters currently available on the market, which
measure the phase difference between voltage and current. When power-factors must be measured, measure
the power, voltage, and current on the input side and output side, then calculate the power-factor using the
following formula:
[%]
]
[
]
[
]
[
100
A
Current
V
Voltage
3
W
Power
factor
Power
´
´
´
=
-
Table 8-3-1 Meters for measuring main circuit
Input (power supply) side
Output (motor) side
DC link circuit
voltage
(P(+) - N(
-
))
Item
Voltage Current
Voltage Current
Meter
name
Ammeter
A
R,S,T
Voltmeter
V
R,S,T
Powermeter
W
R,S,T
Ammeter
A
U,V,W
Voltmeter
V
U,V,W
Powermeter
W
U,V,W
DC voltmeter
V
Meter type
Moving-iron
type
Rectifier or
moving-iron
type
Digital
power meter
Moving-iron
type
Rectifier type
Digital
power meter
Moving-coil type
Symbol
Note: When measuring the output voltage using a rectifier type meter, an error may occur.
Use a digital AC power meter to ensure accuracy.
Figure 8-3-1 Connection of the meters
Содержание 5000VG7S Series
Страница 7: ...0 6 Warning Label Position for Inside the Inverter...
Страница 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Страница 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Страница 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Страница 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...