2-14
Y1
Transistor output 1
Y2
Transistor output 2
Y3
Transistor output 3
Y4
Transistor output 4
Outputs signals such as Running, Speed equivalence, Overload early
warning, ... and
z
as transistor outputs from inverter to specified
ports. For details, see 2.3.2 'Functions of Terminals'.
<Transistor Output Circuit Specifications>
Trans
ist
or ou
tput
CME
Transistor output common
A common terminal for transistor output terminals. Insulated from
terminals CM and 11.
30A,30B,
30C
Alarm relay output
(for any fault)
Outputs alarm signal as relay contact output (1SPDT) when inverter
stops due to alarm.
Contact capacity: 250V AC, 0.3A, cos
f
= 0.3 (or 48V DC, 0.5A when
conformed with Low Voltage Directive)
You may choose to close contacts under unusual or normal
conditions.
Re
la
y o
u
tp
u
t
termi
n
al
s
Y5A,Y5C
Relay output
You may select a signal as you may with Y1 to Y4 terminals.
Contact capacity is the same as with alarm relay output terminals.
RX(+),
RX(
-
)
TX(+),
TX(
-
)
RS485 communication
input/output
Input/output terminals for RS485 communication
Up to 31 inverters may be connected through multi-drop connections.
Terminating resistor (100
W
) can be connected via switch (SW3).
C
o
mmu
ni
cati
on
SD(M)
Communication shield cable
connection
Connected with shielded wires.
PA,PB
Pulse generator 2-phase signal
input
Connected with 2-phase signals from pulse generator
PGP,PGM
Pulse generator power supply
Supplies power (+15V DC (switchable to +12V DC)) to PG.
FA,FB
Pulse generator output
Output pulse generator signal with frequency divided to 1/n. (n is
programmable with function code E29.)
Speed dete
cti
on
CM
Pulse generator output
common
A common terminal for FA and FB.
Temp
eratur
e
d
e
tec
tion
TH1,THC
NTC/PTC thermistor
connection terminals
Monitors motor temperature with NTC and PTC thermistors. For
PTC thermistor, motor overheat protection level can be set with
function code E32.
(1) Input terminals (13, 12, and 11)
1) Shielded wires as short as possible (20m or less) should be used
for cables because these terminals handle weak analog signals
that are very susceptible to external noise. The shields should be
grounded to the earth, as a rule. If the signals are greatly affected
by external induction noise, however, connecting the shields to
terminal 11 may be advantageous.
2) When relay contacts are required in this circuit, use twin contacts
handling weak signals. Do not use contacts at terminal 11.
3) If any of these terminal is connected with an external analog signal
output unit, it may malfunction due to the noise generated by the
inverter, depending on the analog signal output circuit. In this
case, connect a ferrite core or capacitor to the external analog
signal output unit.
Figure 2-3-10
Figure 2-3-11
Protection against Noise (Example)
VR
1k to 5k
W
Item
min.
typ.
max.
ON level
-
1V
2V
Operating
voltage
OFF level
-
24V
27V
On-time max. load current
-
-
50mA
Off-time permissible leak
current
-
-
0.1mA
Содержание 5000VG7S Series
Страница 7: ...0 6 Warning Label Position for Inside the Inverter...
Страница 23: ...2 5 Basic Wiring Diagram Figure 2 3 1 Basic Wiring Diagram...
Страница 36: ...2 18 l Control circuit terminals Control circuit terminals Screw size M3...
Страница 94: ...9 4 FS5941 40 47 Figure 9 1 FS5941 60 52 FS5941 86 52 Figure 9 2...
Страница 96: ...9 6 RF3280 F11 RF3400 F11 Figure 9 5 RF3880 F11 Figure 9 6 6 6 Figure 9 7 F200160...