Installing a NetIron MLX Series Router
December 2008
© 2008 Foundry Networks, Inc.
3-11
CAUTION:
For the NEBS compliant installation of a NetIron XMR 4000, 8000, 16000, and 32000 with AC and
DC system use a ground wire of at least 6 American Wire Gauge (AWG). The ground wire should have an agency-
approved crimped connector (provided with the chassis) attached to one end, with the other end attached to build-
ing ground. The connector must be crimped with the proper tool, allowing it to be connected to both ground screws
on the enclosure. Before crimping the ground wire into the provided ground lug, insure the bare copper wire has
been cleaned and antioxidant is applied to the bare wire.
Figure 3.8 Crimping the Power Supply Wire in the Lug
4.
Re-attach the transparent cover over the power supply lugs that was removed in Step 1.
5.
Connect the wire to your DC power source making sure to connect the -48V cable to the negative terminal on
the power supply and the 0V cable to the positive terminal.
DC return shall be isolated from the chassis ground (DC-I) when connections to the power supply are made.
Final Steps
Here are the final steps to complete in the order listed:
•
“Attaching a Management Station”
•
“Powering-On the Power Source”
•
#8 AWG Power Supply Wire