D.4 The Freshwater - Coolant Circuit
D.4.1 Position of the external Cooling Water Expansion Tank
The Panda generator is normally sup-
plied with an additional, external cool-
ing water expansion tank. This tank
must be installed in such a way that its
lower edge is at least 500mm more
highly arranged than the upper edge of
the sound cover.
If this 500mm should be fallen below,
i.e. the cooling water expansion tank is
lower installed, very large problems
can occur with filling and ventilating.
Extend and displace the hose lines to
the outside or possibly even up to the
deck.
Fig. D.10: Cooling water expansion tank
ATTENTION! The external cooling water expansion tank may be filled only up to the lower
edge of the lower tension tape (see note "max") in the maximum filling level in cold condi-
tion.
D.4.2 De-aerating at the first filling of the internal cooling water circuit
1. For the preparation of filling the following steps are to be undertaken:
a. Open the cooling water cap on the
housing of the water-cooled exhaust
elbow union,
Fig. D.11: Cooling water filler neck