Generator Failure
Page 40 Panda_12mini_PMS_Digital_s00865_Installation manual.V02 - Chapter C: Generator Failure
23.1.07
C.3.1 Adjustment of the maximum engine speed:
1.Disconnect the electrical supply line
to the actuator.
1. Plug for actuator
Fig. C.3: Electrical supply actuator
The picture deviates from the original.
2.Loosen the max speed lock nut with
two spanners size 14mm.
1. Spanner size 14mm
2. Spanner size 14mm
Fig. C.4: Max speed lock
3.Connect a voltmeter (TRMS) with a
display range 300V AC to the AC out-
let between 4 and 1 to the load sokket.
Fig. C.5: Connect voltmeter - 120V/60Hz
1
2x
2
1