Generator Failure
23.1.07
Panda_12mini_PMS_Digital_s00865_Installation manual.V02 - Chapter C: Generator Failure Page 41
4. Ensure no electrical load is connected.
5. Start the generator.
The picture deviates from the original.
6. Increase the speed of the generator by
turning the spiral spindle manually until
the voltmeter shows a value of 260V.
Fig. C.6: Turning spindle
The picture deviates from the original.
7. Turn the limit nut tight to keep the
speed setting.
8. Secure the limit nut with the lock nut.
1. Spanner size 14mm
2. Spanner size 14mm
Fig. C.7: Max speed lock
9. Check the voltage of the generator is limited to max. 260V (without load).
10. Re-adjust if necessary by repeating the procedure.
C.3.2 Adjustment of minimum engine speed
1. Repeat the loosening procedure detailed above on the minimum speed locking and adjusting
nuts.
2. Be sure that no electrical load is connected.
3. Start the generator.
4. Decrease the rev of the generator by turning the spindle of the actuator manually until the volt-
meter shows a value of 200V.
5. Tighten both nuts as before.
6. Check the lower voltage of the generator is limited to min. 200V without load.
7. Re-adjust if necessary.