Remote Control Panda 6-50
Seite/Page 120 - Kapitel/Chapter A: Remote Control Panda 6-50
F1WT1-95E730 Panda 6-50 Fernbedienpanel_eng.fm
Fischer Panda Datasheet
A.3.2
Daily routine checks before starting
1. Oil level control (ideal level: 2/3 of maximum level)
AtTTENTION! OIL PRESSURE CONTROL!
True, the diesel motor automatically switches off when there is a lack of oil, but it is very damaging for the motor, if the oil level drops to
the lowest limit. Air can be sucked in suddenly when the boat rocks in heavy seas, if the oil level is at a minimum. This affects the
grease in the bearings. It is therefore necessary to check the oil level daily before initially running the generator. The oil level must be
topped up to the 2/3 of maximum level, if the level drops below the mark between maximum und minimum levels.
The oil level of the oil cooled bearing must be checked at every operation day before the first starting - see inspection hose
at the generator backend. Service interval 1000hrs.
2. State of cooling water.
The external compensation tank should be filled up to a maximum of in a cold state. It is very important that large expansion area
remains above the cooling water level.
3. Open sea cock for cooling water intake.
For safety reasons, the seacock must be closed after the generator has been switched off. It should be re-opened before starting the
generator.
4. Check raw water filter.
The raw water filter must be regularly checked and cleaned. The impeller fatigue increases, if residual affects the raw water intake.
5. Check all hose connections and hose clamps are leakage.
Leaks at hose connections must be immediately repaired, especially the raw water impeller pump. It is certainly possible that the raw
water impeller pump will produce leaks, depending upon the situation. (This can be caused by sand particles in the raw water etc.) In
this case, immediately exchange the pump, because the dripping water will be sprayed by the belt pulley into the sound insulated
casing and can quickly cause corrosion.
6. Check all electrical lead terminal contacts are firm.
This is especially the case with the temperature switch contacts, which automatically switch off the generator in case of faults. There is
only safety if these systems are regularly checked, and these systems will protect the generator, when there is a fault.
7. Check the motor and generator mounting screws are tight.
The mounting screws must be checked regularly to ensure the generator is safe. A visual check of these screws must be made, when
the oil level is checked.
8. Switch the land electricity/generator switch to zero before starting or switch off all the load.
The generator should only be started when all the load has been switched off. The excitation of the generator will be suppressed, if the
generator is switched off with load connected, left for a while, or switched on with extra load, thus reducing the residual magnetism
necessary for excitation of the generator to a minimum. In certain circumstances, this can lead to the generator being re-excitated by
means of a DC source. If the generator does not excitate itself when starting, then excitation by means of DC must be carried out
again.
9. Check the automatic controls functions and oil pressure.
Removing a cable end from the monitoring switch carries out this control test. The generator should then automatically switch off.
Please adhere to the inspection timetable (see Checklist in the appendix).
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...