Maintenance Instructions
Page 70 AGT 6000 PVMV-N 12V_24V - Chapter C: Maintenance Instructions
C.3 De-aerating the fuel system
Normally, the fuel system is designed to bleed out air itself i.e. as soon as the electric starter
motor starts operation the fuel pump starts working and the fuel system will be de-aerated after
some time automatically. It is nevertheless essential to bleed the system as follows prior to the
first operation (as all hoses are empty):
Switch the main power switch on control panel to „ON“. Functional components must illuminate.
Push failure bypass switch and hold tight. The
electric fuel pump has to be running audibly.
By moving the failure bypass switch you can
hear the solenoid valve of the generator star-
ting and stopping (when the sound cover is
taken off).
Fig. C.3-1: Failure bypass switch
After the fuel pump has been running 3 to 4
minutes because the failure bypass switch
has been pushed down the bleeding screw of
the solenoid valve has to be unscrewed.
When opening the screw one has to carry on
pushing the switch. To avoid fuel getting in
the sound cover a piece of cloth or absorbent
paper should be put under the connection. As
soon as fuel is running out without bubbles
the air bleeding screw can be screwed in
again. Now stop pushing the failure bypass
switch.
Fig. C.3-2: Fuel stop solonoid
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...