Remote Control Panda 6-50
Seite/Page 122 - Kapitel/Chapter A: Remote Control Panda 6-50
F1WT1-95E730 Panda 6-50 Fernbedienpanel_eng.fm
Fischer Panda Datasheet
A.3.4
Stopping the Generator
1. Switch off load.
2. If the load is higher than 70% of the nominal load, the generator temperatures should be stabilised by swit-
ching off the load for at least 5 minutes.
At higher ambient temperatures (more than 25°C) the generator should always run for at least 5 minutes without load, before it is swit-
ched off, regardless of the load.
3. Press „OFF“ button and switch off the generator.
4. Activate additonal switches (Battery switch, fuel stop valve etc.).
NOTE: Never switch off the battery until the generator has stopped.
5. If necessary, close sea cock.
A.3.5
Starting the Generator by a „Failure bypass switch“
See also Generator manual
There is a "pressure switch" on the operation unit. Faults (e.g. caused by overheating) can be manually overcome
by means of this switch. Using the remote control panel can start the generator. The operating temperature can
be reduced for a short period of time (without stress of course), so that the fault switch returns to the original posi-
tion should overheating cause the generator to shut down because of overheating.
ATTENTION:
Before using the failure bypass switch, it is important to check the oil level, since the oil gauge is deactivated by
the switch. For a further reason it is important to switch off the generator electrical load before the generator is
shut down:
Before stopping the generator it is highly recommended that electrical devices (e.g. refrigerating compressors, air
conditioning compressors etc) are switched off, because the voltage drops as the rotational speed (rpm) decrea-
ses as the engine comes to a halt.
(Also see information regarding voltage control with automatic shut-off for protection of consumers when over or
under voltage occurs).
This is also the case when the generator is started when consumers are switched on.
Normally the generators will no longer excitate if a certain amount of base load is stepped up. The electrical load
should also be shut-off before starting the generator.
If started under electrical load, the engine will still run but the generator will not generate the correct voltage (or
even no voltage) since the stator windings do not have the chance to reach full excitation. Electrical units, which
are switched on in this condition, could possibly be damaged (special caution should be practised with electric
motors to avoid burnout).
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...