Maintenance Instructions
AGT 6000 PVMV-N 12V_24V - Chapter C: Maintenance Instructions Page 71
Now the unit can be started by pushing the
"START"-button. The unit should start after
a short while. Should the unit not start the
pipe union nuts of the injection nozzles
has to be loosen and lift the injection pipe
a few millimeter. Try again to start the unit.
After the unit has started the pipe union
nut has to be tightened again.
Fig. C.3-3: Injection nozzle
The injection line must be raised some mil-
limeters.
Main power switch "OFF".
Fig. C.3-4: Injection nozzle
C.3.1 Exchange of the fuel filter
The exchange of the filter depends on the
contamination of the fuel, should take
place at least all 300 operation hours.
Before the exchange of the filter the inlet
must be clamped.
Remove the hoses from the used filter and
fasten them to the new filter. The arrow on
the filter housing indicates the direction of
the fuel flow. A clogged filter causes a
decreased power output of the generator.
Fig. C.3-1: Fuel filter
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...