The Panda Generator
AGT 6000 PVMV-N 12V_24V - Chapter A: The Panda Generator Page 41
A.4.3 Starting Generator
1. If necessary, open the fuel valve.
2. If necessary, close the main battery switch.
3. Check if all the consumers have been switched off.
The consumers are switched off, before the generator is switched off. The generator is not to be started with con-
sumers connected. If necessary, the main switch or fuse should be switched off or the consumers should be indi-
vidually switched off.
4. Press „ON“ button.
Control light for "ON" Button must light up.
5. Pre-heat engine.
Pre-heating is necessary for every running temperature. Pre-heating is not necessary, only if the generator has
just been run. The heating period should take at least 6 seconds, however, 20 seconds at the maximum. Heating
must last for 20 seconds at a temperature of +5°C. If a second attempt is to be made, then a pause of at least 60
seconds is required.
The generator can be started with the assistance of a pre-heating device at temperatures as low as - 20°C.
Please note that the generator can only be run at temperatures below -8°C with winter fuel and additional special
additives.
6. Press „START“ button.
The electric starter may only be used for a maximum of 20 seconds. Thereafter, a pause of, at least, 60 seconds
is required. If the aggregate does not immediately start, then the fuel intake should be checked to ensure it is flo-
wing freely. (For temperatures below - 8°C check whether there is winter fuel)
7. Check circuit-voltmeter, to test whether there is AC-voltage and is within the tolerance rage
(Frequency and voltage).
The AC voltage should be within a tolerance of ± 3 Volt without load at the nominal voltage. When running without
load, the generator frequency should be 4% below the nominal voltage. The generator should be checked, before
the consumers are switched on, if the current remain at this level.
8. Switch on consumers.
The consumers should only be switched on if the generator voltage is within the permissible range. Parallel con-
nection of several consumers should be avoided, especially if there are consumers with electric motors, such as
air-conditioning units in the system. In this case, the consumers must be connected Step by Step.
A.4.4 Stopping the Generator
1. Switch off consumers.
2. If the load is higher than 70% of the nominal load, the generator temperatures should be stabi-
lised by switching off the consumers for at least 5 minutes.
At higher ambient temperatures (more than 25°C) the generator should always run for at least 5 minutes without
load, before it is switched off, regardless of the load.
3. Press „OFF“ button and switch off the generator.
4. Activate additonal switches (Battery switch, fuel stop valve etc.).
Содержание AGT 6000 PVMV-N
Страница 1: ...Panda AGT 6000 PVMV N Super silent technology 24V 6kW Fischer Panda GmbH ...
Страница 6: ......
Страница 10: ...8 Socket wrench set Hexagon wrench keys ...
Страница 92: ...Generator Failure Page 90 AGT 6000 PVMV N 12V_24V Chapter D Generator Failure ...
Страница 100: ...Appendix Page 98 AGT 6000 PVMV N 12V_24V Chapter E Appendix ...
Страница 102: ...Page 100 AGT 6000 PVMV N 12V_24V Chapter E E 6 Capsule Measurements ...
Страница 106: ...VCS AGT U I Page 104 Chapter A VCS AGT U I VCS AGT UI_eng fm Fischer Panda Datasheet blank ...