Document #15140 Rev.G 01/02/02 P/N 15140:G
83
Ademco Contact ID Format Event Code Descriptions
Appendix D
Ademco Contact ID Format Event
Code Descriptions
This appendix describes the various Event Codes and their messages which are available for the Ademco Contact ID
Format.
The reporting structure for the Ademco Contact ID Format is as follows:
SSS 18 QXYZ GG CCC
where
SSSS
= Four digit Subscriber ID Account Code (addresses 17 - 20 and 43 - 46)
18
= Identifies transmission as Contact ID to the receiver at the Central Station
Q
= Event Qualifier where 1 = New Event and 3 = New Restore
XYZ
= Event code (shown in Table 3-3 on page 38 and Table 3-6 on page 43)
GG
= Group number
CCC
= Zone number
Notes:
1.
GG Group Number is fixed at '00' and cannot be changed.
2.
CCC Zone Number is transmitted as '001' for zone one up to '005' for zone five.
Ademco Contact ID Reporting Structure
A typical printout from a Central Station receiver (such as the Ademco 685) of alarm and trouble reports in the
Ademco Contact ID Reporting Structure follows:
Notes:
1.
18
, which is used in the reporting structure to identify the transmission as Contact ID, is not printed out in the
alarm and trouble report.
2.
Q
, which is the Event Qualifier for the reporting structure, is printed out in the report as an E for New Event or
R for New Restore.
Time
Date
Rcvr/Line ID
SSSS
QXYZ
GG
CCCC
11:28
03/25
11
7777
E110
00
C001 - general fire alarm on zone one
11:28
03/25
11
7777
E111
00
C002 - smoke detector alarm on zone two
11:28
03/25
11
7777
E380
00
C003 - fault on zone three
11:28
03/25
11
7777
E570
00
C004 - Zone four disabled
11:28
03/25
11
7777
R110
00
C001 - Zone one alarm restored
11:28
03/25
11
7777
R111
00
C002 - smoke detector zone two restored
11:28
03/25
11
7777
R380
00
C003 - zone three fault restored
11:28
03/25
11
7777
R570
00
C004 - zone four reenabled
11:28
03/25
11
7777
E158
00
C005 - high temperature, zone five
11:28
03/25
11
7777
E151
00
C003 - gas detected, zone three