Document #15140 Rev.G 01/02/02 P/N 15140:G
63
History Mode
5.2
History Mode
All Normal Mode events are stored in a History File list for future recall. Recall is possible via the 4-character dis-
play or via an optional printer. The History File list is a first-in, first-out (FIFO) file. In this manner, only the most
recent events may be called up from memory. Older events will be overwritten, that is, pushed out of the FIFO file.
The number of stored events is 32 maximum. The History File is kept in E
2
memory. Complete power loss will not
erase the list.
Pressing the
MODE
key followed by the code
4478
and then the
[ENTER/STORE]
key places the control panel into
History Mode. This will not occur if there are any active alarm conditions present. The event displayed, is the most
recent event.
☛
4478
spells HIST on a Touch-Tone
®
phone.
Once in History Mode, the control panel will:
✓
Blink the trouble LED
✓
Activate the trouble relay
✓
Disable the Notification Appliance Circuit(s)
✓
Disable the alarm relay
✓
Display all events as they occurred since the last time the History File list was cleared. The most recent
event will be displayed first
✓
Ignore all other keys other than those mentioned in this section
✓
Transmit the 'off normal' message to the Central Station(s)
✓
Continue to communicate any events not previously acknowledged at the Central Station prior to enter-
ing History Mode
The Down Arrow key moves the History File to show older (previous) events. The Up Arrow key moves the History
file to show newer (more recent) events. Following is a list of messages as they will appear on the display:
It should be noted that setting the time and date may cause corruption of the History File contents. The History File
should therefore be cleared after the time and date are set. To clear the list from E
2
memory, press the
SILENCE
key
twice before exiting the History Mode.
A lack of keyboard activity for a period of 10 minutes will cause the control panel to return to Normal Mode. If a
printer is connected to the control panel, the History File will be printed upon successful entry into History Mode and
a list of the most recent 32 events, time and date stamped, will print out.
Note that remote site upload or download is
not possible while the panel is in History Mode.
d__1
d__2
d__3
d__4
d__5
E__1
E__2
E__3
E__4
E__5
A__1
A__2
A__3
A__4
A__5
Zone 1 Disabled
Zone 2 Disabled
Zone 3 Disabled
Zone 4 Disabled
Zone 5 Disabled
Zone 1 Enabled
Zone 2 Enabled
Zone 3 Enabled
Zone 4 Enabled
Zone 5 Enabled
Alarm Zone 1
Alarm Zone 2
Alarm Zone 3
Alarm Zone 4
Alarm Zone 5
Trouble Zone 1
Trouble Zone 2
Trouble Zone 3
Trouble Zone 4
Trouble Zone 5
Annunciator Fault
Earth Fault
Low Battery
No Battery
Primary C.S.# Comm. Fault
Secondary C.S. # Comm. Fault
Bell 1 Fault or Disabled
Bell 2 Fault or Disabled
Primary Phone Line Fault
Secondary Phone Line Fault
F__1
F__2
F__3
F__4
F__5
F__A
F__E
Lo_b
no_b
PH_1
PH_2
bEL1
bEL2
no_1
no_2
Supv. Alarm Zone 1
Supv. Alarm Zone 2
Supv. Alarm Zone 3
Supv. Alarm Zone 4
Supv. Alarm Zone 5
AC Power Loss
Silence Switch Pressed
Reset Switch Pressed
SUP1
SUP2
SUP3
SUP4
SUP5
_AC_
SILE
rES_