Document #15140 Rev.G 01/02/02 P/N 15140:G
45
Programming Options
Zones 1-5 Function Selection (57-61)
The five zones on the control panel may be programmed as shown below. Program entries alter zone function and
transmittal priority.
When using Ademco Contact ID format, Zone Alarm and Zone Restoral event codes change automatically as shown
in Table 3-7 . Be certain to reprogram alarm event codes when selecting process monitoring functions. Zone fault
and disable event codes may also be user reprogrammed (refer to “Ademco Contact ID Format Event Code Descrip-
tions” on page 83)
.
Zone 1 Function Selection (57)
Factory default for zone 1 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 2 Function Selection (58)
Factory default for zone 2 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 3 Function Selection (59)
Factory default for zone 3 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable; '5' for waterflow silenceable; '6' for waterflow
nonsilenceable.
Zone 4 Function Selection (60)
Factory default for zone 4 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Zone 5 Function Selection (61)
Factory default for zone 5 is '0' for 2-wire smoke detector. Enter '1' for pull station; '2' for normally open contact
device; '3' for supervisory; '4' for supervisory autoresettable.
Note: Programming any zone to function as supervisory or supervisory autoresettable will cause the defaulted event
codes (see notes in Table 3-1 through Table 3-5 ) to be automatically changed. The defaulted code of '1' is changed
to '8' for formats 3+1 and 4+1 Standard and Expanded, 4+2 Expanded and 4+1 Express. The defaulted codes of 11,
12, 13, 14 and 15 are changed to 81, 82, 83, 84 and 85 accordingly for formats 4+2 Standard and 4+2 Express.
Waterflow Retard Timer (62-63)
A delay may be added prior to declaring a waterflow type of alarm. Delays up to 89 seconds are allowed. The
default for addresses 62 and 63 are '00' (no additional delay). Valid entries for address 62 are 0-8 and for address 63
are 0-9. Program entries into these addresses only if entering a '5' or '6' in address 59.
Be careful to include any built-
in delays of the waterflow device.
TABLE 3-7:
Zone Function Selection
Program Entry
Function
Zone Alarm/Restoral
1
Event Code
1. Ademco Contact ID format selection causes Event Codes to automatically change to values shown in Table 3-7 .
0
Operates 2-wire smoke detectors
111
1
Pull station
115
2
Normally open contact device
110
3
Supervisory
200
4
Supervisory autoresettable - self restore function, is not latched by the
control panel
200
5
Waterflow silenceable - silencing of silenceable NACs allowed (affects
zone 3 only)
113
6
Waterflow nonsilenceable - silencing of silenceable NACs is not allowed.
Must clear waterflow alarm condition and press the reset key (affects zone
3 only)
113