Central Station Communications
60
Document #15140 Rev.G 01/02/02 P/N 15140:G
4.4.1 Transmittal Priorities
The integral communicator transmits highest priority events first. Events, in terms of priority, are listed below in
descending order:
1.
Alarms (highest priority level)
✓
Pull stations
✓
Waterflow
✓
Smoke detector
✓
Other alarm types
2.
Supervisory Zone
3.
System Troubles
✓
Zone disabled
✓
Fire drill
✓
AC fail (after delay)
✓
Zonal faults
✓
Earth fault
✓
Low battery/no battery
✓
Telephone line fault
✓
Notification Appliance Circuits fault
✓
Communication trouble
✓
Annunciator trouble
✓
System off normal
4.
Restoral Reports
✓
Zone alarm
✓
Supervisory
✓
Zone(s) enabled
✓
Fire drill
✓
AC
✓
Zone fault
✓
Earth
✓
Battery
✓
Telephone line
✓
Notification Appliance Circuits
✓
Communication
✓
Annunciator trouble
✓
System off normal
5.
24 Hour Test (lowest priority)
Red LEDs are provided on the control panel circuit board to identify which telephone line is activated. Also, a green
LED labeled 'kissoff' will turn on whenever the control panel has successfully transmitted reports to the Central Sta-
tion. The 'kissoff' LED may turn on several times during communications with a Central Station.