Document #15140 Rev.G 01/02/02 P/N 15140:G
35
Programming Options
Valid entries for both the primary and secondary phone numbers are 0 - F with the numeric digits as dialed numbers
and the alpha-characters representing the following functions:
A = * on a Touchtone phone keypad
B = # on a Touchtone phone keypad
C = look for secondary dial tone for up to two seconds (then dial anyway)
D = 3-second pause
E = 5-second pause
F = end of phone number (Note: F must be entered)
Primary Central Station Number Communication Format (16)
One location is needed to select the Communication Format for the primary phone number. Address 16 is used for
this purpose. The default (factory setting) for this address is 'E' for Ademco Contact ID format. '0' through 'E' may be
entered in place of the default entry. After making the selection, press the
[ENTER/STORE]
key to store the selec-
tion. The available format options are as follows:
0: 4+1 Ademco Express Standard, DTMF, 1400/2300 ACK
1: 4+2 Ademco Express Standard, DTMF, 1400/2300 ACK
2: 3+1 Standard 1800 Hz Carrier, 2300 Hz ACK
3: 3+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
4: 3+1 Standard 1900 Hz Carrier, 1400 Hz ACK
5: 3+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
6: 4+1 Standard 1800 Hz Carrier, 2300 Hz ACK
7: 4+1 Expanded 1800 Hz Carrier, 2300 Hz ACK
8: 4+1 Standard 1900 Hz Carrier, 1400 Hz ACK
9: 4+1 Expanded 1900 Hz Carrier, 1400 Hz ACK
A: 4+2 Standard 1800 Hz Carrier, 2300 Hz ACK
B: 4+2 Expanded 1800 Hz Carrier, 2300 Hz ACK
C: 4+2 Standard 1900 Hz Carrier, 1400 Hz ACK
D: 4+2 Expanded 1900 Hz Carrier, 1400 Hz ACK
E: Ademco Contact ID, DTMF, 1400/2300 ACK
F: Not Used
Note: Consult your Central Station for proper selection or consult our factory representatives. For any format cho-
sen, the control panel automatically programs all of the event codes. Refer to Table 3-1 through Table 3-5 .