Operation
56
Document #15140 Rev.G 01/02/02 P/N 15140:G
4.3.8 Zone Disable/Enable
The zone disable feature may be used to disable any zone in the system. Zones may be disabled if they are normal, in
trouble or alarmed.
Zones may be disabled only during the Normal Mode of operation, when the fire protection is
active. If the panel is in alarm, the silence switch must be pressed first, before the zone disable feature will function.
To disable a zone, press the
MODE
key once (the display will go blank). You then have 10 seconds to start entering
the code
3472
. Next press the
[ENTER/STORE]
key.
☛
3472
spells DISA on a Touch-Tone
®
phone.
A flashing lower case
d
will appear on the far left of the display. Press the digit key corresponding to the zone num-
ber to be disabled. The number will appear on the far right of the display. Press
[ENTER/STORE]
to disable the
zone. Note that the trouble relay is activated and the trouble LED blinks.
The zone disable message will remain on the display until the zone is reenabled. To reenable a zone, press the
MODE
key. The display will go blank. You then have 10 seconds to start entering the code
3622
. Next, press the
[ENTER/STORE]
key.
☛
3622
spells ENAB on a Touch-Tone
®
phone.
A flashing upper case
E
will appear on the left of the display. Press the digit key corresponding to the zone number to
be enabled. The number will appear on the far right of the display. Press the
[ENTER/STORE]
key to reenable the
zone. Not that the trouble relay is restored to normal and the trouble LED turns off (if no other troubles are on the
system).
4.3.9 Fire Drill
The Drill (manual evacuate) feature turns on both Notification Appliance Circuits (if programmed as enabled) and
turns off the silence LED. Tor perform a fire drill, press the
MODE
key followed by the code
3745
then the
[ENTER/STORE]
key. The display will indicate
dril
. The alarm relay is not activated for a fire drill. There is an
option to transmit the fire drill report code to the Central Station.
☛
3745
spells DRIL on a Touch-Tone
®
phone.
During a fire drill, the Silence key will silence both NACs and the Reset key restores the control panel to normal.
All
zones remain active during a fire drill.