Switch Functions
34
Document #15140 Rev.G 01/02/02 P/N 15140:G
Note that address location 56 is factory defaulted to '0' for 'control panel only.' This keeps the communicator off until
location 56 is changed to '1' for 'slave communicator' or '2' for 'panel/communicator.' Once location 56 is set to '1' or
'2' and a valid phone number is entered, entry into the Program Mode will cause transmission of the 'system off nor-
mal' report.
When viewing any address in Program Mode, the first three digits on the left of the display represent the memory
address which can be 00 to 374 (alpha-characters are not used). The last digit, farthest right, represents the contents
of the memory address. The first address and contents displayed upon entering Program Mode are shown below:
3.2
Switch Functions
The function of each keypad key in Program Mode is shown below.
3.3
Programming Options
Primary Central Station Phone Number (00-15)
The first sixteen addresses (00-15) are factory set to 'F' (
00_F
to
15_F
). Programming this feature is typically done as
follows: If the phone number to be entered is 484-7161, press
4
. The display will read
00_4
. Press
[ENTER/
STORE]
to save the entry to memory and increment to the next address
01_F
.
Enter the remaining numbers in their respective addresses as shown below:
00_F
(address)(data)
FIGURE 3-1:
Control Panel Keypad
No function in
Program Mode
Address entry keys are 0 - 9
Data entry keys are 0 - 9 and
A - F
Select operating mode
Increment memory address
Decrement memory address
One press = first memory address
Two presses = type any address
Save data, go to next address
4
8
4
7
1
6
1
F
F
F
F
F
F
F
F
F
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15
Phone Number
Addresses