Programming Reference Sheets
76
Document #15140 Rev.G 01/02/02 P/N 15140:G
Appendix B
Programming Reference Sheets
❐
00
❐
01
❐
02
❐
03
❐
04
❐
05
❐
06
❐
07
❐
08
❐
09
❐
10
❐
11
❐
12
❐
13
❐
14
❐
15
Addresses 00 to 15 store the Primary Central Station Phone Number.
Enter 'F' to represent the end of the number.
❐
16
Primary Central Station Communication Format:
Enter '0 - F'.
❐
17
❐
18
❐
19
❐
20
Primary Central Station Account Code:
Valid entries are '0 - F'.
❐
21
❐
22
❐
23
❐
24
Primary Central Station 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❐
25
Primary Number Test Time Interval.
Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
❐
26
❐
27
❐
28
❐
29
❐
30
❐
31
❐
32
❐
33
❐
34
❐
35
❐
36
❐
37
❐
38
❐
39
❐
40
❐
41
Addresses 26 to 41 store the Secondary Central Station Phone Number.
Enter 'F' to represent the end of the number.
❐
42
Secondary Central Station Communication Format:
Enter '0 - F'.
❐
43
❐
44
❐
45
❐
46
Secondary Central Station Account Code:
Valid entries are '0 - F'.
❐
47
❐
48
❐
49
❐
50
Secondary Central Station 24-Hour Test Time.
Enter military time (i.e. 1400 for 2 PM).
❐
51
Secondary Number Test Time Interval.
Enter '0' for 24 hour; '1' for 12 hour; '2' for 8 hour; '3' for 6 hour.
❐
52
Alarm Verification.
Enter '0' for no verification; '1' for verification of all 2-wire smoke zones.
❐
53
❐
54
❐
55
Future use.
❐
56
Slave Communicator/Fire Panel Selection.
Enter '0' for fire panel only; '1' for slave communicator only; '2'
for fire panel/communicator operation.
❐
57
Zone 1 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
58
Zone 2 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
59
Zone 3 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable); '5' for waterflow (silenceable); '6'
for waterflow (nonsilenceable).
❐
60
Zone 4 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
61
Zone 5 Function Select.
Enter '0' for 2-wire smoke detectors; '1' for pull station; '2' for normally open contact
devices; '3' for supervisory devices; '4' for supervisory devices (autoresettable).
❐
62
❐
63
Waterflow Retard timer.
Enter 0 - 89 additional seconds.
❐
64
AC Loss Delay.
Enter '0' for 6 hour delay; '1' for 7 hours; '2' for 8 hours; '3' for 9 hours; '4' for 10 hours; '5'
for 11 hours; '6' for 12 hours; '7' for 15 hours; '8' for 16 hours; '9' for 17 hours; 'A' for 18 hours; 'B' for 19 hours; 'C'
for 20 hours; 'D' for 21 hours; 'E' for 22 hours; 'F' for 23 hours.
❐
65
Alarm Presignal.
Enter '0' to disable alarm presignal; '1' to enable.
❐
66
❐
67
❐
68
Alarm Presignal Delay Timer.
Enter 0 - 179 additional seconds (default - 120 seconds).
❐
69
Notification Appliance Circuit #1 Selection.
Enter '0' for enabled (silenceable); '1' for enabled (nonsilence-
able); '2' for disabled.
...To enter Programming Mode, press the
MODE
key, the code
7764
and then the
[ENTER/STORE]
key...