Product Description
10
Document #15140 Rev.G 01/02/02 P/N 15140:G
CHAPTER 1
Product Description
The MS-5024UD is a combination FACP (Fire Alarm Control Panel) and DACT (Digital Alarm Communicator
Transmitter) all on one circuit board. It is a five-zone panel which uses conventional input devices. The panel
accepts waterflow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally
open contact devices. Outputs include two NACs (Notification Appliance Circuits), alarm and trouble relays, super-
visory and communicator failure relay drivers.
The integral communicator transmits system status (alarms, troubles, AC loss, etc.) to UL-listed Central Stations via
the public switched telephone network. The control panel has a built-in programmer and may also serve as a slave
communicator to a host panel. It also supervises all wiring, AC voltage, telephone line input voltage and battery
level.
The control panel may be programmed or interrogated off-site via the public switched telephone network. Any IBM
compatible personal computer with DOS
™
4.01 or greater plus Windows
™
3.1 or greater, with a 1200 baud Hayes
™
compatible modem and Fire•Lite Upload/Download software P/N PK-5024UD, may serve as a Service Terminal.
This allows download of the entire program or upload of the entire program, history file, walktest data, current status
and system voltages. The MS-5024UDE offers the same features as the MS-5024UD but allows connection to 220/
240 VAC input.
1.1
Product Features
• Selectable as Fire Panel, Fire Panel/Communicator or Slave Communicator
• Programmable Zone ID: 2-wire smoke, pull station, normally open contact device, supervisory, supervisory
autosilence, waterflow silenceable or waterflow nonsilenceable
• One Style D (Class A) zone
• Four Style B (Class B) zones
• 3.6 amps usable power expandable to 5.6 amps
• Optional 5-zone Relay Module (RM-5F)
• CAC-5F Style D (Class A) Zone Converter Module
• Two NFPA Style Y (Class B) or Style Z (Class A) Notification Appliance (bell) Circuits
• Built-in programmer
• Built-in voltmeter
• Telephone Line Active LED indicators
• Communication confirmation (Kissoff) LED
• Disable report by event
• Programmable event codes
• 24 volt operation
• Real-Time clock and calendar
• Trouble reminder
• Alarm verification
• RZA-5F remote annunciator (requires ADM-24 Annunciator Driver Module)
• Small size - 15" (38.1 cm) x 14.5" (36.83 cm) x 2.75" (6.985 cm)
• History file with 32 event storage
• Silence inhibit per NAC (Notification Appliance Circuit)
• Autosilence per NAC