Programming Options
48
Document #15140 Rev.G 01/02/02 P/N 15140:G
FAX/Answer Machine, Primary Phone Line (106)
This entry is used when the primary phone line is being shared with a FAX, answering machine or other device. Fac-
tory default is '0' for no sharing of the primary phone line. An entry of '1' indicates sharing and allows the panel to
wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Service Terminal Number 2 Phone Number (107-122)
Addresses 107 through 122 are reserved for the Service Terminal phone number 2. Factory default is all 'Fs'. Valid
entries are 0-9 plus A, B, C, D and E, similar to the primary and secondary Central Station phone number entries pro-
grammed at addresses 00-15 and 26-41. Use 'F' to designate the end of the phone number.
Ring Count on Secondary Phone Line (123-124)
Use this address to designate the number of rings allowed on the secondary phone line prior to answering an incom-
ing call from a Service Terminal. Factory default is '03' which means the panel will not answer an incoming call until
3 rings are detected. This entry may be programmed up to a maximum of 25 rings. A setting of '00' prevents the
panel from answering incoming calls.
FAX/Answer Machine, Secondary Phone Line (125)
This entry is used when the secondary phone line is being shared with a FAX, answering machine or other device.
Factory default is '0' for no sharing of the secondary phone line. An entry of '1' indicates sharing and allows the panel
to wait for three consecutive calls from the Service Terminal, spaced 30 seconds apart, before responding.
Upload/Download Reports Sent to Secondary Central Station Phone Number, Backup or Always (126)
Reports for request for 'upload/download', 'successful upload', 'successful download' and 'failed upload/download' are
always sent to the primary Central Station phone number. This entry allows for the same reports to either always be
sent to the secondary Central Station phone number or only if attempts to transmit to the primary Central Station
phone number are unsuccessful. Factory default is '0' for backup only. Enter '1' for always.
Programming Event Codes (127-374)
The type of reports and event codes that are sent to the Central Station are in Table 3-1 through Table 3-5 . The
selections made for the Primary Central Station Number Communication Format (address 16) and the Secondary
Central Station Number Communication Format (address 42) automatically program addresses 127-374 with factory
default selections.
Any of the event codes may be changed.
Consult your Central Station prior to altering the event codes
. Entering an
event code of '0' will cause the communicator to NOT transmit the report. For the 3+1, 4+1 and 4+1 Express formats
or the 4+2 Expanded format, enter '0'. For the 4+2 Standard or 4+2 Express formats, enter '00'. Transmission of
reports to
either or both
Central Station phone numbers may be disabled.
Note the special 'System Abnormal Test Report' event code. This report was added per new UL DACT requirements.
This report is generated in place of the normal test report when an alarm and/or trouble condition exists at the time
the test report is due to be sent.
Programming the Real-Time Clock and Calendar
Entering an address greater than 374 will cause a display of the current time. On initial power-up, the clock will start
running from the factory setting of 00:01 (military time). The far left digit will be flashing, indicating that this is the
first digit to be programmed.
It should be noted that setting the time and date may cause corruption of the History
File. For this reason, it is important that the History File be cleared after the time and date has been set. Refer to
“History Mode” on page 63.
Hours/Minutes
Select a digit then press
[ENTER/STORE]
. The digit 2nd from the left will start flashing. Select a digit then press
[ENTER/STORE]
. Hours setting is complete. With the digit 2nd from the right flashing, select a digit then press
[ENTER/STORE]
. The digit on the far right will start flashing. Select a digit then press
[ENTER/STORE]
. Min-
utes setting is complete.