Document #15140 Rev.G 01/02/02 P/N 15140:G
15
Optional Devices
1.5.3 Transformer Assembly
One 100VA transformer is provided standard with the panel (3.6 amps
maximum). An optional 100VA transformer, XRM-24 (XRM-24E for
MS-5024UDE), is available to provide maximum accessory power (6.6
amps maximum).
1.5.4 Batteries
The cabinet provides space for 7 Amp Hour batteries (for 12 Amp Hour
up to 18 Amp Hour batteries, use the listed BB-17F battery box). Batter-
ies must be ordered separately.
1.6
Optional Devices
1.6.1 RM-5F Five-Zone Relay Module
The RM-5F option module provides five Form-C relays which track zones 1 through 5. The module mounts to con-
nector J7 on the lower right side of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and
Figure 2-16 on page 31.
1.6.2 CAC-5F Class A Converter Module
The CAC-5F Class A Converter module converts the Style B (Class B) Initiating Device Circuits to Style D (Class
A). The CAC-5F mounts to terminal block TB2, located in the upper center of the main circuit board. The remov-
able terminal block on the CAC-5F module provides for ease of wiring. Refer to Figure 2-17, “CAC-5F Style D Con-
verter,” on page 32
1.6.3 ADM-24 Annunciator Driver Module
The ADM-24 Annunciator Driver Module supports the RZA-5F Remote Annunciator module. Annunciator wiring is
supervised for open circuits by this module. The Annunciator Driver Module mounts to connector J3 in the upper
right corner of the main circuit board. Refer to Figure 1-2, “MS-5024UD Panel,” on page 12 and Figure 2-11 on page
28.
1.6.4 RZA-5F Remote Annunciator
The RZA-5F Remote Annunciator mounts on a standard single-gang box and provides LED indication of the
following:
• Alarm Zone 1 (red)
• Alarm Zone 2 (red)
• Alarm Zone 3 (red)
• Alarm Zone 4 (red)
• Alarm Zone 5 (red)
• System Trouble (yellow)
A Local Trouble Sounder and Tone Silence Switch are also provided. All LEDs and their wiring are supervised for
open conditions. Any open condition will cause the System Trouble LED to illuminate. Slide-in paper labels permit
an easy change of zone information. Refer to Figure 2-12, “RZA-5F,” on page 28, Figure 2-13 on page 29 and Figure
2-14 on page 29.
Note that the Remote Annunciator requires the use of the ADM-24 Annunciator Driver Module.
FIGURE 1-4:
XRM-24(E) Transformer
Standard
Transformer
Optional
Transformer
XRM-24(E)