Site Preparation
Extreme Networks Consolidated XOS Hardware Installation Guide
22
Mechanical Recommendations for the Rack
Use distribution racks that meet the following mechanical recommendations:
●
Use an open style, 19-inch (48.26 cm) rack to facilitate easy maintenance and to provide proper
ventilation.
●
Use a rack made of steel or aluminum.
●
The rack should use the universal mounting rail hole pattern that is identified in IEC Standard 297.
●
The rack should have designated earth grounding connections (typically on the base).
●
The rack must meet earthquake safety requirements equal to that of the installed chassis.
●
The mounting holes should be flush with the rails to accommodate the chassis.
●
Install equipment into the lower half of the rack first to avoid making the rack top-heavy.
●
The rack should support approximately 600 pounds (272 kilograms).
Protective Grounding for the Rack
Use a rack grounding kit and a ground conductor that is carried back to earth or to another suitable
building ground.
All Extreme Networks switches are designed with mounting brackets that provide solid metal-to-metal
connection to the rack. If you do not use equipment racks, you can attach wiring terminals directly to
the mounting brackets for appropriate grounding. Extreme Networks switches have grounding
terminals that are mounted on the back of the chassis.
At minimum, follow these guidelines:
●
Ground equipment racks to earth ground.
■
CAD weld appropriate wire terminals to building I-beams or earth ground rods.
■
Use 8 AWG copper stranded wire.
■
Drill and tap wire terminals to equipment racks.
■
Position the earth ground as close to the equipment rack as possible to maintain the shortest
wiring distance possible.
■
Use a ground impedance tester or micro-ohm meter to test the quality of earth ground
connection at the chassis. This will insure good grounding between the chassis, rack, and earth
ground.
NOTE
Because building codes vary worldwide, Extreme Networks strongly recommends that you consult an electrical
contractor to ensure proper equipment grounding for your specific installation.
Space Requirements for the Rack
Provide enough space in front of and behind the switch so that you can service it easily. Allow a
minimum of 48 inches (122 cm) in front of the rack and 24 inches (61 cm) behind the rack. When using a
relay rack, provide a minimum of 24 inches (61 cm) of space behind the mounted equipment. Extra
room on each side is optional.
Содержание BlackDiamond 8810
Страница 8: ...Table of Contents Extreme Networks Consolidated XOS Hardware Installation Guide 8...
Страница 12: ...Preface Extreme Networks Consolidated XOS Hardware Installation Guide 12...
Страница 13: ...1 Site Preparation...
Страница 14: ......
Страница 36: ...Initial Management Access Extreme Networks Consolidated XOS Hardware Installation Guide 36...
Страница 37: ...2 Common Characteristics...
Страница 38: ......
Страница 57: ...3 BlackDiamond 10K Series Switch...
Страница 58: ......
Страница 76: ...BlackDiamond 10K System Chassis Extreme Networks Consolidated XOS Hardware Installation Guide 76...
Страница 100: ...BlackDiamond 10K Series I O Modules Extreme Networks Consolidated XOS Hardware Installation Guide 100...
Страница 105: ...4 Aspen Switch...
Страница 106: ......
Страница 136: ...Aspen 8810 MSM and I O Modules Extreme Networks Consolidated XOS Hardware Installation Guide 136...
Страница 147: ...5 Appendixes...
Страница 148: ......
Страница 157: ...Extreme Networks Consolidated XOS Hardware Installation Guide 157...
Страница 158: ...Technical Specifications Extreme Networks Consolidated XOS Hardware Installation Guide 158...