ProNet Plus Series AC Servo User's Manual
- 206 -
Parameter
No.
Description
Setting
Validation
Control
Mode
Function and Meaning
terminal enabled
Pn512.2
CN1_17
Pn512.3
CN1_18
Pn513.0
CN1_19
Pn513
Bus
control
input
terminal enabled
Immediately
P, S, T
Pn514
Input port filter
Immediately
P, S, T
It is used to set input port filter time. The signal will be
lagged if the parameter setting is too high.Unit:0.2ms
Pn515
Alarm port filter
Immediately
P, S, T
It is used to set alarm port filter time, The signal will be
lagged if the parameter setting is too high.Unit:0.2ms
Pn516
Input port signal
inversion
Immediately
P, S, T
[0]: Do not inverse signal.
[1]: Inverse signal
Pn516.0
CN1_15 inversion
Pn516.1
CN1_16 inversion
Pn516.2
CN1_17 inversion
Pn516.3
CN1_18 inversion
Pn517.0
CN1_19 inversion
Pn517
Input port signal
inversion
Immediately
P, S, T
Pn518
Dynamic brake time
Immediately
P, S, T
Motor dynamic brake time Unit: ms
Pn519
Serial encoder error
time
Immediately
P, S, T
In the range of this parameter, there will be no warning
of serial encoder error Unit: 0.1ms
Pn520
Position
complete
time
Immediately
P, S, T
This parameter set position complete time Unit: 0.1ms
Pn521
Binary
After restart
P,S,T
Pn521.0 If connected externally regenerative resistor
0: connect externally regenerative resistor between B1
and B2
1: Dose not connect externally regenerative resistor,
relay on internal capacitance.
(This parameter is in effect only on
ProNet-A5/01/02/04)
Pn521.1 Reserved
Pn521.2 Reserved
Pn521.3 Reserved
Pn522
Reserved
—
—
—
Pn523
Reserved
—
—
—
Pn524
Reserved
—
—
—
Pn525
Overload alarm
threshold
Immediately
P, S, T
When load percentage is larger than overload alarm
threshold, A04 will occur soon.
Pn525 is recommended to set below 120, otherwise
the servo drive and motor will be damaged.
Unit:%
Pn526
Temperature
threshold of motor
overheat alarm
Immediately
P, S, T
When servomotor winding temperature exceeds
Pn526 setting, A19 will occur. Unit:
℃
(Only enabled in ProNet
–75/1A/1E/2B)