ProNet Plus Series AC Servo User's Manual
- 172 -
Parameter
No.
Description
Setting
Validation
Control
Mode
Function and Meaning
Speed reference
Error counter
Pn500
Pn500
Pn111
Pn111
Pn112
Feedforward
Immediately
P
It is used to set position feedforward. The response
speed is faster and position error is less when this
parameter setting is higher. Vibration will occur if the
value is set too large.
Unit: %
Pn113
Feedforward filter
time constant
Immediately
P
It is used to ease mechanical vibration due to position
feedforward. The feedforward lag will be enlarged and
result to vibration if the value is set too large.
Unit: 0.1ms
Pn114
Torque feedforward
Immediately
P, S
It is used to set torque feedforward, and enhance
response speed.
Set the load inertia ratio (Pn106) correctly to enable
this function in manual gain adjustment mode.
Unit: %
Pn115
Torque feedforward
filter time constant
Immediately
P, S
It is used to ease mechanical vibration due to torque
feedforward.
Unit: 0.1ms
Pn116
P/PI switching
condition
After restart
P, S
[0]Torque reference percentage
[1]Value of offset counter
[2]Value of acceleration speed setting
[3]Value of speed setting
[4]Fixed PI
Pn117
Torque switching
threshold
After restart
P, S
Threshold of torque to switch PI control to P control.
Unit: %
Pn118
Offset counter
switching threshold
Immediately
P
Threshold of error counter to switch PI control to P
control.
Unit: puls
Pn119
Setting acceleration
speed switching
threshold
Immediately
P, S
Threshold of acceleration speed to switch PI control to
P control.
Unit: 10rpm/s
Pn120
Setting speed
switching threshold
Immediately
P, S
Threshold of speed to switch PI control to P control.
Unit: rpm
Pn121
Gain switching
After restart
P, S
[0]Fix to 1st group gain