GD350A series high-performance multifunction VFD
-78-
Function
code
Name
Description
Default
through keypad
Output torque
-250.0–250.0%
0.0%
Torque reference
value
-300.0–300.0% (of the motor rated current)
0.0%
5.5.6 Motor parameters
Check the safety conditions surrounding the motor and load machineries before
autotuning as physical injury may occur due to sudden start of motor during
autotuning.
Although the motor does not run during static autotuning, the motor is still supplied
with power. Do not touch the motor during autotuning; otherwise, electric shock
may occur. Do not touch the motor before autotuning is completed.
If the motor has been connected to a load, do not carry out rotary autotuning.
Otherwise, the VFD may malfunction or may be damaged. If rotary autotuning is
carried out on a motor which has been connected to a load, incorrect motor
parameter settings and motor action exceptions may occur. Disconnect from the
load to carry out autotuning if necessary.
The VFD can drive both asynchronous motors and synchronous motors, and it supports two sets of
motor parameters, which can be switched over by multifunction digital input terminals or
communication modes.