GD350A series high-performance multifunction VFD
-146-
Function
code
Name
Description
Default Modify
fmax
Output frequency f
t1
t2
Time t
1: S curve. The output frequency increases
or decreases according to the S curve.
The S curve is generally applied to elevators,
conveyors, and other application scenarios
where smoother start or stop is required.
Output frequency f
Time t
fmax
t1
t2
Note:
If mode 1 is selected, set P01.06,
P01.07, P01.27, and P01.28 accordingly.
P01.06
Time of starting
segment of ACC S
curve
The curvature of S curve is determined by
the ACC range and ACC/DEC time.
Output frequency f
Time t
t1
t2
t3
t4
t1=P01.06
t2=P01.07
t3=P01.27
t4=P01.28
Setting range: 0.0–50.0s
0.1s
◎
P01.07
Time of ending
segment of ACC S
curve
0.1s
◎
P01.08
Stop mode
0: Decelerate to stop. After a stop command
takes effect, the VFD lowers output frequency
based on the DEC mode and the defined
DEC time; after the frequency drops to the
stop speed (P01.15), the VFD stops.
1: Coast to stop. After a stop command takes
effect, the VFD stops output immediately; and
the load coasts to stop according to
mechanical inertia.
0
○