GD350A series high-performance multifunction VFD
-184-
Function
code
Name
Description
Default Modify
P07.09
Rotational speed
display coefficient
0.1–999.9%
Mechanical rotation speed = 120 * (Displayed
running frequency) *×P07.09/(Number of
motor pole pairs)
100.0%
○
P07.10
Linear speed
display coefficient
0.1–999.9%
Linear speed = (Mechanical rotation speed) ×
P07.10
1.0%
○
P07.11
Rectifier bridge
temperature
-20.0–120.0°C
●
P07.12
Inverter
temperature
-20.0–120.0°C
●
P07.13
Control board
software version
1.00–655.35
●
P07.14
Local accumulative
running time
0–65535h
●
P07.15
VFD electricity
consumption high-
order bits
Used to display the electricity consumption of
the VFD.
VFD electricity consumption =
P07.15*1000+P07.16
Setting range of P07.15: 0–65535 kWh
(*1000)
Setting range of P07.16: 0.0–999.9 kWh
●
P07.16
VFD electricity
consumption low-
order bits
●
P07.17
Reserved
Reserved
P07.18 VFD rated power 0.4–3000.0kW
●
P07.19 VFD rated voltage 50–1200V
●
P07.20 VFD rated current 0.1–6000.0A
●
P07.21 Factory bar code 1 0x0000–0xFFFF
●
P07.22 Factory bar code 2 0x0000–0xFFFF
●
P07.23 Factory bar code 3 0x0000–0xFFFF
●
P07.24 Factory bar code 4 0x0000–0xFFFF
●
P07.25 Factory bar code 3 0x0000–0xFFFF
●
P07.26 Factory bar code 4 0x0000–0xFFFF
●
P07.27 Present fault type 0: No fault
1: Inverter unit U-phase protection (OUt1)
2: Inverter unit V-phase protection (OUt2)
●
P07.28
Last fault type
●
P07.29 2nd-last fault type
●