GD350A series high-performance multifunction VFD
-221-
Function
code
Name
Description
Default Modify
P17.39
Function code in
parameter
download error
0.00–99.00
0.00
●
P17.40 Motor control mode
Ones place: Control mode
0: Vector control 0
1: Vector control 1
2: Space voltage vector control
3: Closed-loop vector control
Tens place: Control status
0: Speed control
1: Torque control
2: Position control
Hundreds place: Motor number
0: Motor 1
1: Motor 2
0x2
●
P17.41
Electromotive
torque upper limit
0.0%–300.0% (of the motor rated current)
180.0%
●
P17.42
Braking torque
upper limit
0.0%–300.0% (of the motor rated current)
180.0%
●
P17.43
Forward rotation
upper-limit
frequency
in torque control
0.00–P00.03
50.00Hz
●
P17.44
Reverse rotation
upper-limit
frequency
in torque control
0.00–P00.03
50.00Hz
●
P17.45
Inertia
compensation
torque
-100.0%–100.0%
0.0%
●
P17.46
Friction
compensation
torque
-100.0%–100.0%
0.0%
●
P17.47
Motor pole pairs 0–65535
0
●
P17.48
VFD overload count
value
0–65535
0
●
P17.49 Frequency set by A 0.00–P00.03
0.00Hz
●