GD350A series high-performance multifunction VFD
-292-
Function
Address
Data description
R/W
2006H
Setting of the upper limit of the reverse running
frequency (0–Fmax, unit: 0.01 Hz)
R/W
2007H
Upper limit of the electromotion torque (0–3000,
1000 corresponding to 100.0% of the motor rated
current)
R/W
2008H
Upper limit of the brake torque (0–3000, 1000
corresponding to 100.0% of the motor rated
current)
R/W
2009H
Special control command word:
Bit0–1: =00: Motor 1 =01: Motor 2
Bit2: =1 Enable speed/torque control switchover
=0: Disable speed/torque control switchover
Bit3: =1 Clear electricity consumption
=0: Not clear electricity consumption
Bit4: =1 Pre-excitation; =0: Disable pre-excitation
Bit5: =1 DC brake =0: Disable DC brake
R/W
200AH
Virtual input terminal command, range: 0x000–
0x3FF
Corresponding to S8/S7/S6/S5/HDIB/HDIA/S4/
S3/ S2/S1
R/W
200BH
Virtual output terminal command, range: 0x00–
0x0F
Corresponding to local RO2/RO1/HDO/Y1
R/W
200CH
Voltage setting (used for V/F separation)
(0–1000, 1000 corresponding to 100.0% of the
motor rated voltage)
R/W
200DH
AO output setting 1 (-1000–+1000, 1000
corresponding to 100.0%)
R/W
200EH
AO output setting 2 (-1000–+1000, 1000
corresponding to 100.0%)
R/W
VFD status word 1
2100H
0001H: Forward running
R
0002H: Reverse running
0003H: Stopped