GD350A series high-performance multifunction VFD
-212-
Function
code
Name
Description
Default Modify
M≥400%,
protection
is
performed
immediately.
1m
1h
116%
200%
Time t
Motor overload multiple
Setting range: 20.0% –120.0%
P12.28
Power display
calibration
coefficient of motor
2
0.00–3.00
1.00
○
P12.29
Parameter display
selection of motor 2
0: Display by motor type. In this mode, only
parameters related to the present motor type
are displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0
○
P12.30
System inertia of
motor 2
0–30.000kgm2
0.000
○
P12.31–
P12.32
Reserved
0–65535
0
○
P13 group––SM control
P13.00
SM injection current
drop rate
Used to set the reduction rate of the injection
reactive current. When the active current of
the SM increases to some extent, the injection
reactive current can be reduced to improve the
power factor of the motor.
Setting range: 0.0%–100.0% (of the motor
rated current)
80.0%
○
P13.01
Initial pole detection
method
0: Invalid
1: Pulse detection method
2: Pulse detection method
0
◎
P13.02
Pull-in current 1
Pull-in current is the pole positioning current.
Pull-in current 1 is valid within the lower limit
20.0%
○