GD350A series high-performance multifunction VFD
-167-
Function
code
Name
Description
Default Modify
the motor rated voltage)
Setting range of P04.32: 0.0%–P04.31
P04.33
Weakening
coefficient in
constant power
zone
1.00–1.30
1.00
○
P04.34
Pull-in current 1 in
SM V/F control
When the SM V/F control mode is enabled, the
function code is used to set the reactive
current of the motor when the output
frequency is lower than the frequency
specified by P04.36.
Setting range: -100.0%–100.0% (of the motor
rated current)
20.0%
○
P04.35
Pull-in current 2 in
SM V/F control
When the SM V/F control mode is enabled, the
function code is used to set the reactive
current of the motor when the output
frequency is higher than the frequency
specified by P04.36
Setting range: -100.0%–100.0% (of the motor
rated current)
10.0%
○
P04.36
Frequency
threshold for pull-in
current switching in
SM V/F control
When the SM V/F control mode is enabled,
the function code is used to set the frequency
threshold for the switching between pull-in
current 1 and pull-in current 2.
Setting range: 0.00Hz–P00.03 (Max. output
frequency)
50.00Hz
○
P04.37
Reactive current
closed-loop
proportional
coefficient in SM
V/F control
When the SM V/F control mode is enabled,
the function code is used to set the
proportional coefficient of reactive current
closed-loop control.
Setting range: 0–3000
50
○
P04.38
Reactive current
closed-loop integral
time in SM V/F
control
When the SM V/F control mode is enabled, the
function code is used to set the integral
coefficient of reactive current closed-loop
control.
Setting range: 0–3000
30
○
P04.39
Reactive current When the SM V/F control mode is enabled, the
8000
○