GD350A series high-performance multifunction VFD
-196-
Function
code
Name
Description
Default Modify
4: ACC/DEC time 4
P09 group–– PID control
P09.00
PID reference
source
When the frequency command selection
(P00.06, P00.07) is 7 or the voltage setting
channel selection ((P04.27) is 6, the VFD is
process PID controlled.
The function code determines the target given
channel during the PID process.
0: Keypad (P09.01)
1: AI1
2: AI2
3: AI3
4: High-speed pulse HDIA
5: Multi-step running
6: Modbus/Modbus TCP communication
7:
Profibus/CANopen/DeviceNet
communication
8: Ethernet communication
9: High-speed pulse HDIB
10: EtherCAT/Profinet/EtherNetIP
communication
11: Programmable expansion card
12: Reserved
The set target of process PID is a relative
value, for which 100% equals 100% of the
feedback signal of the controlled system.
The system always calculates a related value
(0–100.0%).
0
○
P09.01
PID reference
preset through
keypad
The function code is mandatory when
P09.00=0. The base value of The function
code is the feedback of the system.
Setting range: -100.0%–100.0%
0.0%
○
P09.02
PID feedback
source
The function code is used to select PID
feedback channel.
0: AI1
1: AI2
2: AI3
3: HDIA
0
○