GD350A series high-performance multifunction VFD
-209-
Function
code
Name
Description
Default Modify
stall
P11.21
Proportional
coefficient of
voltage regulator
during overvoltage
stall
Used to set the proportional coefficient of the
bus voltage regulator during overvoltage stall.
Setting range: 0–1000
60
○
P11.22
Integral coefficient
of voltage regulator
during overvoltage
stall
Used to set the integral coefficient of the bus
voltage regulator during overvoltage stall.
Setting range: 0–1000
10
○
P11.23
Proportional
coefficient of
current regulator
during overvoltage
stall
Used to set the proportional coefficient of the
active current regulator during overvoltage
stall.
Setting range: 0–1000
60
○
P11.24
Integral coefficient
of current regulator
during overvoltage
stall
Used to set the integral coefficient of the active
current regulator during overvoltage stall.
Setting range: 0–2000
250
○
P11.25
Enabling VFD
overload integral
0: Disable
1: Enable
When the function code is set to 0, the
overload timing value is reset to zero after the
VFD is stopped. In this case, the
determination of VFD overload takes more
time, and therefore the effective protection
over the VFD is weakened.
When the function code is set to 1, the
overload timing value is not reset, and the
overload timing value is accumulative. In this
case, the determination of VFD overload takes
less time, and therefore the protection over the
VFD can be performed more quickly.
0
◎
P11.26
Reserved
0–65536
0
○
P11.27
VF vibration control
method
0x00–0x11
Ones place:
0: Method 1
0x00
◎