GD350A series high-performance multifunction VFD
-317-
type input selection and voltage type input selection of AI1, and they can be selected through J2. "AIO"
and "AVO" are the current type output selection and voltage type output selection of AO1, and they
can be selected through J5. "120" indicates 120
Ω
terminal resistor, and it can connect to J1. By default,
J1 connects to NC, J2 to AV, and J5 to AVO.
PE
485-
485+
AI1
AO1
COM
COM
PS1
PS2
PS3
PRO2A
PRO2C
PW
24V
PS4
PS5
PS6
PRO1A
PRO1C
Indicator definition:
Indicator
Name
Function
LED1
Power indicator
(Green)
This indicator is on when the expansion card is
powered on.
LED3
Communication
indicator (Green)
This indicator is on when the expansion card is
establishing a connection with the control
board; it blinks periodically after the expansion
card is properly connected to the control board
(the period is 1s, on for 0.5s, and off for the
other 0.5s); and it is off when the expansion
card is disconnected from the control board.
LED4
Error indicator (Red)
This indicator blinks when an error occurs (the
blinking period is 1s, on for 0.5s, and off for the
other 0.5s). You can query the error types on
the upper computer Auto Station.
This indicator is off when there is no error.
LED5
Power indicator
This indicator is on when the expansion card is
powered on.
LED6
RUN indicator (Green)
This indicator is on when the PLC program is
running; it is off when the PLC program stops.
The EC-PC502-00 programmable expansion card can replace some micro PLC applications. It adopts
the global mainstream development environment PLC, supporting the instruction language (IL), ladder
diagram (LD), and sequential function chart (SFC). It provides a user program storage space of 16K
steps and data storage space of 8K words, and supports saving data of 1K words at power failure,
which facilitate customers' secondary development and meets the customization requirements.
The EC-PC502-00 programmable expansion card provides 6 digital inputs, 2 relay outputs, 1 analog