GD350A series high-performance multifunction VFD
-77-
Function
code
Name
Description
Default
torque upper limit motor rated current)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Modbus/Modbus TCP communication (same as
the above)
6: Profibus/CANopen/DeviceNet communication
(same as the above)
7: Ethernet communication (same as the above)
8: Pulse frequency HDIB (same as the above)
9: EtherCat/Profinet/EtherNetIP communication
10: Programmable expansion card
11: Reserved
Note:
For setting methods 1–10, 100% corresponds
to three times the motor rated current.
Setting source of
braking torque
upper limit
0: Keypad (P03.21)
1: AI1 (100% corresponding to three times the
motor rated current)
2: AI2 (same as the above)
3: AI3 (same as the above)
4: Pulse frequency HDIA (same as the above)
5: Modbus/Modbus TCP communication (same as
the above)
6: Profibus/CANopen/DeviceNet communication
(same as the above)
7: Ethernet communication (same as the above)
8: Pulse frequency HDIB (same as the above)
9: EtherCat/Profinet/EtherNetIP communication
10: Programmable expansion card
11: Reserved
Note:
For setting methods 1–10, 100% corresponds
to three times the motor rated current.
0
Electromotive
torque upper limit
set through
keypad
0.0–300.0% (of the motor rated current)
180.0%
Braking torque
upper limit set
0.0–300.0% (of the motor rated current)
180.0%