GD350A series high-performance multifunction VFD
-61-
Function
code
Name
Description
Default
5: Modbus/Modbus TCP communication (same as the
above)
6: Profibus/CANopen/DeviceNet communication
(same as the above)
7: Ethernet communication (same as the above)
8: Pulse frequency HDIB (same as the above)
9: EtherCAT/Profinet communication
10: Programmable expansion card
11: Reserved
Note:
For setting methods 1–10, 100% corresponds to
three times the motor rated current.
Setting source
of braking
torque upper
limit
0: Keypad (set by P03.21)
1–10: Same as those for P03.18
0
Electromotive
torque upper
limit
set through
keypad
0.0–300.0% (of the motor rated current)
180.0%
Braking
torque upper
limit set
through
keypad
180.0%
Weakening
coefficient in
constant
power zone
0.1–2.0
0.3
Lowest
weakening
point in
10%–100%
20%