GD350A series high-performance multifunction VFD
-153-
Function
code
Name
Description
Default Modify
P02.27
Overload protection
coefficient of motor
1
Motor overload multiples M=Iout/(In*K)
In is rated motor current, lout is VFD output
current, and K is motor overload protection
coefficient.
A smaller value of K indicates a bigger value
of M.
When M=116%, protection is performed after
motor overload lasts for 1 hour; when
M=200%, protection is performed after motor
overload lasts for 60 seconds; and when
M≥400%,
protection
is
performed
immediately.
1m
1h
116%
200%
Time t
Motor overload multiple
Setting range: 20.0% –120.0%
100.0%
○
P02.28
Power display
calibration
coefficient of motor
1
The function code can be used to adjust the
power display value of motor 1. However, it
does not affect the control performance of the
VFD.
Setting range: 0.00–3.00
1.00
○
P02.29
Parameter display
selection of motor 1
0: Display by motor type. In this mode, only
parameters related to the present motor type
are displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0
○
P02.30
System inertia of
motor 1
0–30.000kgm2
0
○
P02.31–
P02.32
Reserved
0–65535
0
○
P03 group––Vector control of motor 1