GD350A series high-performance multifunction VFD
-71-
Function
code
Name
Description
Default
communication
12: Programmable expansion card
13: Reserved
Voltage set
through keypad
0.0%–100.0%(of the motor rated voltage)
100.0%
Voltage increase
time
0.0–3600.0s
5.0s
Voltage decrease
time
0.0–3600.0s
5.0s
Max. output
voltage
P04.32–100.0% (of the motor rated voltage)
100.0%
Min. output voltage 0.0%–P04.31 (the motor rated voltage)
0.0%
Weakening
coefficient in
constant power
zone
1.00–1.30
1.00
Pull-in current 1 in
SM V/F control
When the SM V/F control mode is enabled, the
function code is used to set the reactive current
of the motor when the output frequency is lower
than the frequency specified by P04.36.
Setting range
:
-100.0%–100.0% (of the motor
rated current)
20.0%
Pull-in current 2 in
SM V/F control
When the SM V/F control mode is enabled, the
function code is used to set the reactive current
of the motor when the output frequency is higher
than the frequency specified by P04.36.
Setting range
:
-100.0%–100.0% (of the motor
rated current)
10.0%
Frequency
threshold for pull-in
current switching in
SM V/F control
When the SM V/F control mode is enabled, the
function code is used to set the frequency
threshold for the switching between pull-in
current 1 and pull-in current 2.
Setting range
:
0.00Hz–P00.03 (Max. output
frequency)
50.00Hz
Reactive current
closed-loop
proportional
When the SM V/F control mode is enabled, the
function code is used to set the proportional
coefficient of reactive current closed-loop
50