Prosonic S FMU95
Commissioning
E Hauser
67
"LVL N state" (N = 1 - 10)
"level N" (N = 1 - 10)
Displays the currently measured level.
"act. distance N" (N = 1 - 10)
Displays the currently measured distance.
"status"
Use this parameter to define the status of the interference echo suppression.
•
enable map
Choose this option in order activate the interference echo suppression. The mapping is then used
for signal evaluation.
•
disable map
Choose this option in order to deactivate the interference echo suppression. The mapping is then
no longer used for signal evaluation but it can be reactivated if required.
•
delete map
Choose this option in order to delete the mapping. It can not be reactivated again and the
instrument uses the preprogrammed default mapping.
6.2.4
Envelope curve display
After the basic setup an evaluation of the measurement with the aid of the envelope curve is
recommended,
6.2.5
Deactivation of unused sensor inputs
!
Note!
Sensor management
For instruments with multiple sensor inputs it is possible to deactivate inputs (or sensors) which are
not used. To do so, go to the function "sensor management/FDU sensor N/sensor operation" and
select the desired option:
•
on
The sensor is switched on.
•
hold
The sensor is switched off. The last measured value is held.
•
off
The sensor is switched off. No measured value is transmitted.
LVL1 state
L100C
level 1:
act. distance 1:
status: