"LVL N sensor selection" (N = 1 - 10)
"input"
Use this parameter to assign a sensor to the channel.
Selection:
• no sensor
• sensor 1
• ...
• sensor 10
"sensor selection"
Use this parameter to specify the type of the connected ultrasonic sensor.
!
Note!
• For the sensors
FDU9x
the option "automatic" is recommended (default setting). With this setting
the Prosonic S recognizes the type of sensor automatically.
• For the sensors
FDU8x
the type has to be assigned explicitly. The automatic sensor recognition
does not work for these sensors.
"
Caution!
After
exchanging a sensor
, observe the following:
The automatic sensor recognition is also active after a sensor has been exchanged
3)
. The Prosonic S
recognizes the type of the new sensor automatically and changes the "detected" parameter if
required. The measurement continues without a break.
Nevertheless, in order to ensure perfect measurement, the following checks are required:
• Check the
"empty calibration"
and
"full calibration"
parameters. Adjust these values if
required. Take into account the blocking distance of the new sensor.
• Go to the
"LVL N check value"
parameter set (last set of the basic setup) and check the
displayed distance. If required, perform a new interference echo suppression.
"detected" (only available for "sensor selection" = "automatic")
Indicates the type of the automatically detected sensor.
LVL1 sensor sel.
L1003
input:
sensor selection:
detected:
3)
if the new sensor is of the type FDU9x