Prosonic S FMU95
Commissioning
E Hauser
59
"LVL N linearisation" (N = 1 - 10)
The "linearization" is used to convert the level into other quantities. Especially, it can calculate the
volume or mass within a vessel of arbitrary shape. The Prosonic S provides different linearization
modes for the most common types of vessels. Additionally, a linearization table for arbitrarily shaped
vessels can be entered.
"type"
Use this parameter to select the type of linearisation.
Selection:
•
none
In this linearization type the measured level is not converted but displayed in the selected level
unit (see above, "unit level").
•
linear
In this linearization type the displayed value is proportional to the measured level.
The following additional parameter have to be specified:
– the unit for the linearized value, e.g. kg, m
3
, ft
3
, ... (
"customer unit"
)
– the maximum capacity (a) of the vessel, measured in the customer unit (
"maximum scale"
).
LVL 1 linearisat.
L1008
type:
mode:
!
Note!
Number and type of the parameters in this set depend on the
selected linearization type.
Only the parameters "type" and "mode" are always present.
100%
20
mA
0%
0/4
mA
(a)
kg
m
ft
3
3