Prosonic S FMU95
Commissioning
E Hauser
51
6.2.3
Basic setup
Overview
The following table gives an overview of the basic setup for level measurements. Detailed
information on the parameters can be found in the sections 6.3.2. to 6.3.11.
Step
Parameter Set
Parameter
Remarks
page
Configuring the sensor
1
LVL N sensor selection
(N = 1 - 10)
input
Allocate a sensor to the channel.
sensor selection
Specify the type of sensor ("automatic" for FDU9x)
detected
only available for "sensor selection" = "automatic";
indicates the detected type of sensor.
2
LVL N application parameter
(N = 1 - 10)
tank shape
Select the appropriate values for your application
medium property
process conditions
3
LVL N empty calibration
(N = 1 - N)
empty E
Specify the distance between the sensor membrane and the minimum level
(0%).
4
LVL N full calibration
(N = 1 - 10)
full F
Specify the distance between the minimum (0%) and maximum (100%)
level.
blocking distance (BD)
Display parameter; the maximum value for the full calibration is:
F
max
= E - BD
5
LVL N unit
(N = 1 - 10)
unit level
Select the unit for the level measurement.
level N (N = 1 - 10)
Displays the currently measured level.
sensor
Displays the currently measured distance between the sensor membrane and
the product level.
Linearisation (if no linearisation is required: continue by step 7: "distance correction")
6
LVL N linearisation
(N = 1 - 10)
type
Select type of linearisation
mode
Specify, to which value the measurement refers:
"level" or "ullage"
customer unit
Specify the unit for the linearized value;
(not available for "type" = "none")
max. scale
Specify the maximum contents of the vessel (in customer units);
(not available for "type" = "none")
diameter
Specify the diameter of the tank;
(only available for "type" = "horizontal cylinder" or "sphere")
intermediate height
Specify the intermediate height of the tank or silo;
(only available for "type" = "pyramid bottom", "conical bottom" oder "angled
bottom")
edit
Used to enter, change or delete a linearisation table;
(only available for "type" = "table")
status table
Enables or disables the linearisation table;
(only available for "type" = "table")